mcr Monsun - axial smoke exhaust fan

Fire resistance classes:

  • class F200 – fire resistance 200°C/120 min.
  • class F300 – fire resistance 300°C/60 min.
  • class F400 – fire resistance 400°C/120 min.

Certificate of constancy of performance 1488-CPR-0345/W for F300 and F200.

Certificate of constancy of performance 1488-CPR-0129/W for F400, F300, F200.

Functional properties according to EN 12101-3:2002+AC:2005.

Patent No. 216872 issued by the Patent Office of the Republic of Poland.

Declaration of performance 001-01-CPR-2015.

Declaration of performance 002-01-CPR-2015.

 

mcr Monsun axial fans are used in fire ventilation systems for smoke exhaust and air supply.

Smoke exhaust fans are used for exhausting hot air, smoke and gases occurring in rooms during fire. They facilitate the process of evacuating humans from fire zone, as well as firefighting operations carried out by fire brigades. They also protect the building structure and its equipment from the effect of high temperature, and prevent spreading of fire to rooms under fire.

The devices are adapted for outdoor as well as indoor operation, in vertical and horizontal position.

The fans may also be used in the so-called "smoke tank" - they may operate in the fire zone.

  • possibility of vertical and horizontal installation
  • possibility of adjusting rotor blades every 1° ensures obtaining the assumed operation point
  • comprehensive, certified accessories
  • adapted for work in smoke tank and outside smoke tank
  • available diameters: 355, 400, 450, 500, 560, 630, 710, 800, 900, 1000, 1120, 1250 mm
  • max. efficiency up to 170 000 m3/h
  • max. compression up to 1 300 Pa
  • nominal power 0.55 kW - 90 kW
  • rotation speeds n = 750; 1000; 1500; 3000 RPM
  • IP 55 protection class

Detailed technical specifications are contained in the technical catalogue.

  • Production halls and warehouses
  • Logistics centers
  • Public buildings
  • Commercial buildings
  • Residential buildings

Making variants:

  • one-speed
  • two-speed

Accessories:

  • SW installation feet for horizontal installation
  • KD elastic joints - vibration compensators in F400 class
  • PK counterflanges for duct installation
  • KS, KS-V automatic backdraft dampers
  • PP structures for vertical installation
  • TH/R noise dampers
  • WS service switches (available also in F400 class for working in smoke tank)
  • AM/BM vibration insulators
  • DS grated suction nozzles
  • SO cover grates
  • WO grated outlet stub pipes